Product Name
LinePower RC 3000

Product Code
A03-OP3000-RC (v2.1)

Power Rating (VA)
3000

Power Rating (W)
• Vin=210-265 ---- 2700 W
• Vin=185-300 ---- 2400 W
• Vin=160-300 ---- 2100 W

Input
• Voltage: 170-276V
• Frequency: 50Hz±5%

Output
• Voltage: 200/208/220/230/240±1%
• Frequency: ±1Hz or ±1Hz (Selectable)
• Waveform: Pure SineWave
• Crest Ratio: 3:1
• Harmonic Distortion: min3% @ 100% Liner Load / min7% @100% NON Liner Load

Transfer Time
• AC->DC: 0 ms (True Online Topology)
• nverter->ByPass: 4 ms

Overload
Line Mode (Vin=210-265):
• <105%
• 106%-120% for 30s then ByPass
• 121%-150% for 10s then ByPass
• >150% immediately ByPass
• Buzzer continuously alarm
Battery:
• <105%
• 106%-120% for 30s then shuts down
• 121%-150% for 10s then shuts down
• >150% immediately shuts down
• Buzzer continuously alarm
ByPass:
• <105%
• 106%-120% for 250s then shuts down
• 121%-130% for 125s then shuts down
• 131%-135% for 50s then shuts down
• 136%-145% for 20s then shuts down
• 146%-188% for seconds then shuts down
• >188% immediately shuts down
• Buzzer continuously alarm

Battery
• Voltage: 72 V
• Capacity: 12V/7.0Ah
• Quantity: 6
• Backup Time min (50%,70%, 100%): 6 - 3 - 1
• Type: Sealed Maintenance Free Lead Acid VRLA Type
• Charge Current: 1 A
• Recharging Time: 4 hours to (90%)

Efficency
• Line Mode: Up to 92%
• Eco Mode: Up to 96%
• Battery Mode: Up to 86%

Display LCD
4 LED [Utility Normal, Backup, Fault, Battery Fault]
LCD [ECO, Normal, Battery,OverLoad, Alarm, Service, ByPass, Programmable Outlet1/2, Self-Test, Load/Battery/Vin/Vout/Fin/Fout level, Error, Status]

Diagnostics
Power ON, Front Panel (Select), SW, 24hrs (routine check)

Protection
• In Normal Mode/Battery Short Circuit (LOAD) Electronic Circuit or output Circuit breaker
• In ByPass Mode input Circuit breaker
• Spike Suppression Meets EN61000-4-5
• Battery Over-drain Two stages: Controlled Battery Low Warning & Cut Off Battery Overcharge
• OverTemperature [ Normal mode ->to ByPass, Battery mode-> UPS shuts down]
• Overload AC Buzzer continuously alarms (every 3 Seconds)

Function
• Normal/ECO/CF60Hz/CF50Hz
• DC Start

Alarm
• Battery Mode (sound every 1.5 seconds)
• Low Battery (sound every 0,2 seconds)
• OverLoad (sound every 3 seconds)
• Fault (Continuous tone)

Input Connection
1xIEC (16A, IEC 320-C20)

Output Connection
(Battery Power Supplied) Output 6xIEC (10A, IEC 320-C13)

PC Connection
RS232 (Read and write)
USB (Read)

EPO
YES

Extended Interface Slot
Yes (for SNMP card A03-SNMP-IN)

Extended Battery Connector
YES (A03-BB1)

Programmable Outlet
Yes (2)

Noise Level
Less than 55dB (Active FAN)

Dimensions (WxHxD)
440 x 88 x 600 mm

Net Weight
26,5 Kg

Rack (U)
2U

Temperature Range
0°C ~ 40°C

Humidity
0% ~ 95% (non Condensing)

Package Contents
• LinePower RC 3000
• 2x IEC Cables
• 1x Schuko Cable
• 1x USB Cable
• 1x RS232 Cable